UNIMA CABLE | Low Voltage Power Cables
(N)2XY FR (IEC)
TECHNICAL DATA SHEET
Flame Retardant Copper Power Cable with XLPE Insulation and PVC Sheath | 0.6/1 kV

PRODUCT DESCRIPTION
(N)2XY FR (IEC) is a low-voltage power cable with bare copper conductors, XLPE DIX3 insulation and a black, UV-resistant PVC ST2 outer sheath.
Designed for fixed installation indoors, outdoors, underground and in water.
The cable provides flame-retardant properties according to IEC 60332-3-24, Category C, and a maximum conductor operating temperature of +90°C.
Suitable for industrial installations, building infrastructure and low-voltage power distribution systems.
CABLE CONSTRUCTION
| Conductor | Bare Copper |
|---|---|
| Conductor Class | Class 1; Class 2 from 25 mm² |
| Insulation | XLPE DIX3 |
| Outer Sheath | PVC ST2 |
| Sheath Colour | Crna |
| Core Identification | VDE 0293 / HD 308 |
| UV Resistance | Yes |
| Flame Retardancy | IEC 60332-3-24, Category C |
TECHNICAL DATA
| Radni napon | 0.6/1 kV |
|---|---|
| Max. System Voltage | 1.2 kV |
| Test Voltage | 4 kV |
| Max. Conductor Temp. | +90°C |
| Fixed Cable Temp. | -35°C to +70°C |
| Moved Cable Temp. | -5°C to +70°C |
| Min. Bending Radius | 15 × D |
| Flame Retardancy | IEC 60332-3-24, Cat. C |
| UV Resistance | Yes |
| Materijal vodiča | Copper |
STANDARDS
- Cable Standard|IEC 60502
- Flame Retardancy|IEC 60332-3-24, Category C
- Flame Propagation|VDE 0482-266-2-4
- Core Identification|VDE 0293 / HD 308
APPLICATIONS
- Low-voltage power distribution
- Fixed industrial installations
- Residential and commercial buildings
- Indoor and outdoor installations
- Underground cable installations
- Installation in water
- Electrical infrastructure requiring flame-retardant cables