UNIMA CABLE | Low Voltage Power Cables
(N)2XCY
TECHNICAL DATA SHEET
XLPE Insulated Copper Power Cable with Concentric Copper Conductor | 0.6/1 kV

0.6/1 kV Rated Voltage
Bare Copper Conductors
Concentric Copper Conductor
XLPE DIX3 Insulation
PRODUCT DESCRIPTION
(N)2XCY is a 0.6/1 kV low-voltage power cable with bare copper conductors, cross-linked polyethylene (XLPE DIX3) insulation, a concentric copper conductor and a black PVC DMV5 outer sheath.
The cable is designed for fixed installation indoors, outdoors, in the ground, in water and in concrete. It is flame-retardant, UV-resistant and suitable for permanent low-voltage power distribution systems.
The conductor construction is Class 1 for smaller cross-sections and Class 2 from 25 mm². The maximum conductor operating temperature is +90°C, with a maximum short-circuit conductor temperature of +250°C.
CABLE CONSTRUCTION
| Main Conductor | Bare Copper (Cu) |
|---|---|
| Conductor Construction | Class 1; Class 2 from 25 mm² |
| Insulation | XLPE DIX3 |
| Concentric Conductor | Copper (Cu) |
| Outer Sheath | PVC DMV5 |
| Sheath Colour | Crna |
| Core Identification | Colours according to HD 308; numbered cores for more than 5 cores |
| Meter Marking | Yes |
TECHNICAL DATA
| Radni napon | 0.6/1 kV |
|---|---|
| Max. System Voltage | 1.2 kV |
| Test Voltage | 4 kV |
| Max. Conductor Temp. | +90°C |
| Short-Circuit Temp. | +250°C |
| Fixed Temp. Range | -30°C to +70°C |
| Moving Temp. Range | -5°C to +70°C |
| Min. Bending Radius | 12 × D |
| Max. Tensile Stress | 50 N/mm² |
| Conductor Resistance (20°C) | 1.15 Ω/km |
| Current in Air (30°C) | 100 A |
| Current in Ground (20°C) | 113 A |
| UV Resistant | Yes |
| Outdoor Use | Yes |
| Meter Marking | Yes |
STANDARDS
- Cable Standard|VDE 0276-603 (with reference to)
- CPR Classification|Eca according to EN 50575
- Flame Retardance|VDE 0482-332-1-2 / IEC 60332-1-2
- Core Identification|HD 308
APPLICATIONS
- (N)2XCY is designed for fixed installation indoors, outdoors, directly in the ground, in water and in concrete.
- Suitable for low-voltage power distribution installations requiring copper conductors, XLPE insulation and a concentric copper conductor.