UNIMA CABLE | TECHNICAL DOCUMENTATION
JE-H(St)H FE180/E30-E90
TECHNICAL DATA SHEET
JE-H(St)H FE180/E30-E90 | Halogen-Free Screened Fire Resistant Signal Cable | 225 V Peak

PRODUCT DESCRIPTION
JE-H(St)H FE180/E30-E90 is a halogen-free, screened fire-resistant signal and communication cable with solid copper conductors (0.8 mm), FRNC HI1 insulation, foil screening with drain wire and a red FRNC HM2 outer sheath.
Designed for fixed installation in fire alarm, fire detection and safety communication systems in public, commercial and industrial buildings.
The cable provides FE180 fire resistance and E30-E90 circuit integrity when installed with an appropriately tested cable support system in accordance with DIN 4102-12. Maximum peak operating voltage is 225 V.
CABLE CONSTRUCTION
| Conductor | Bare copper, Class 1 solid, 0.8 mm diameter |
|---|---|
| Core Insulation | Fire-resistant halogen-free FRNC compound, HI1 |
| Core Arrangement | Conductors twisted into pairs; pairs arranged in layers or sub-units |
| Core Identification | Colour coding according to VDE 0815 |
| Screen | Overall foil screen with drain wire |
| Outer Sheath | Halogen-free flame-retardant FRNC compound, HM2 |
| Sheath Colour | Red |
TECHNICAL DATA
| Cable Designation | JE-H(St)H FE180/E30-E90 |
|---|---|
| Peak Operating Voltage | 225 V |
| Materijal vodiča | Bare Copper |
| Conductor Construction | Class 1 Solid |
| Conductor Diameter | 0.8 mm |
| Core Insulation | FRNC HI1 |
| Screening | Overall Foil Screen with Drain Wire |
| Outer Sheath | FRNC HM2 |
| Sheath Colour | Red |
| Maximum Operating Capacitance | 120 nF/km |
| Fixed Installation Temperature | -5°C to +50°C |
| Minimum Bending Radius | 7.5 x Outer Diameter |
| Fire Resistance | FE180 |
| Circuit Integrity | E30-E90 (Tested Installation System) |
| Halogen-Free | IEC 60754 |
| Smoke Emission | IEC 61034 |
| Flame Propagation | IEC 60332-3-24 |
| CPR Classification | According to Applicable Manufacturer DoP |
| Product Standard | VDE 0815 |
STANDARDS
- VDE 0815 – Cable construction and core identification
- DIN 4102-12 – E30-E90 circuit integrity in tested installation systems
- FE180 – Fire resistance classification
- IEC 60332-3-24 – Flame propagation test
- IEC 61034 – Smoke density
- IEC 60754 – Halogen and acidic gas emissions
APPLICATIONS
- Fire alarm and fire detection systems
- Fire safety signal transmission
- Emergency communication systems
- Public buildings with high fire safety requirements
- Hospitals and healthcare facilities
- Schools and educational buildings
- Commercial and industrial facilities
- Fixed installation in dry and damp indoor areas
- Certified cable support systems requiring E30-E90 circuit integrity