UNIMA CABLE
UNIMA CABLE | TECHNICAL DOCUMENTATION

H07V-K – Fleksibilni PVC instalacijski kabel

TECHNICAL DATA SHEET

H07V-K | Flexible PVC Insulated Single Core Wire | 450/750 V | Class 5 Copper | CPR Eca

H07V-K  Flexible PVC Insulated Single Core Wire
PRODUCT DESCRIPTION

H07V-K is a flexible single-core PVC insulated installation wire rated 450/750 V, manufactured with bare copper Class 5 fine-stranded conductors and PVC TI1 insulation.

Designed for laying in protective conduits on or under plaster, in closed installation ducts and for internal wiring of machinery, switchgear and distribution systems.

The wire is flame-retardant according to IEC 60332-1-2 and classified Eca under EN 50575.

Available cross-sections range from 1.5 mm2 to 240 mm2.

Maximum conductor temperature is +70°C. Minimum bending radius for fixed installation is 4 times the approximate outer diameter.

Direct laying under plaster without protective conduit is not permitted.

CABLE CONSTRUCTION
ConductorBare Copper, Class 5 Fine Stranded
Number of Cores1
InsulationPVC Compound TI1
Insulation ColourVarious Colours According to Product Variant
Outer SheathNone - Single Insulated Wire
Radni napon450/750 V
CPR ClassificationEca
TECHNICAL DATA
Cable DesignationH07V-K
Tip kabelaFlexible PVC Insulated Single Core Wire
Rated Voltage U0/U450/750 V
Test Voltage2.5 kV
Materijal vodičaBare Copper
Conductor ConstructionClass 5 Fine Stranded
InsulationPVC TI1
Number of Cores1
Cross-Section Range1.5-240 mm2
Maximum Conductor Temperature+70C
Fixed Installation Temperature-5C to +70C
Moving Temperature+5C to +70C
Minimum Bending Radius, Fixed4 x Outer Diameter
Maximum Operating Capacitance100 nF/km
Flame RetardanceIEC 60332-1-2
CPR ClassificationEca
Product StandardDIN EN 50525-2-31
Conductor StandardDIN EN IEC 60228
Current-Carrying CapacityVDE 0298-4, Table 11
STANDARDS
  • DIN EN 50525-2-31 – PVC Insulated Single Core Wires
  • DIN EN IEC 60228 – Class 5 Copper Conductors
  • EN 50575 – CPR Reaction-to-Fire Classification
  • IEC 60332-1-2 – Flame Propagation
  • VDE 0298-4 – Current-Carrying Capacity Reference
APPLICATIONS
  • Building Electrical Installations
  • Installation in Protective Conduits
  • Closed Installation Ducts
  • Electrical Distribution Boards
  • Switchgear Internal Wiring
  • Machinery Internal Wiring
  • Control Cabinet Wiring
  • Fixed Protected Electrical Installations