H07V-K – Fleksibilni PVC instalacijski kabel
TECHNICAL DATA SHEET
H07V-K | Flexible PVC Insulated Single Core Wire | 450/750 V | Class 5 Copper | CPR Eca

H07V-K is a flexible single-core PVC insulated installation wire rated 450/750 V, manufactured with bare copper Class 5 fine-stranded conductors and PVC TI1 insulation.
Designed for laying in protective conduits on or under plaster, in closed installation ducts and for internal wiring of machinery, switchgear and distribution systems.
The wire is flame-retardant according to IEC 60332-1-2 and classified Eca under EN 50575.
Available cross-sections range from 1.5 mm2 to 240 mm2.
Maximum conductor temperature is +70°C. Minimum bending radius for fixed installation is 4 times the approximate outer diameter.
Direct laying under plaster without protective conduit is not permitted.
| Conductor | Bare Copper, Class 5 Fine Stranded |
|---|---|
| Number of Cores | 1 |
| Insulation | PVC Compound TI1 |
| Insulation Colour | Various Colours According to Product Variant |
| Outer Sheath | None - Single Insulated Wire |
| Radni napon | 450/750 V |
| CPR Classification | Eca |
| Cable Designation | H07V-K |
|---|---|
| Tip kabela | Flexible PVC Insulated Single Core Wire |
| Rated Voltage U0/U | 450/750 V |
| Test Voltage | 2.5 kV |
| Materijal vodiča | Bare Copper |
| Conductor Construction | Class 5 Fine Stranded |
| Insulation | PVC TI1 |
| Number of Cores | 1 |
| Cross-Section Range | 1.5-240 mm2 |
| Maximum Conductor Temperature | +70C |
| Fixed Installation Temperature | -5C to +70C |
| Moving Temperature | +5C to +70C |
| Minimum Bending Radius, Fixed | 4 x Outer Diameter |
| Maximum Operating Capacitance | 100 nF/km |
| Flame Retardance | IEC 60332-1-2 |
| CPR Classification | Eca |
| Product Standard | DIN EN 50525-2-31 |
| Conductor Standard | DIN EN IEC 60228 |
| Current-Carrying Capacity | VDE 0298-4, Table 11 |
- DIN EN 50525-2-31 – PVC Insulated Single Core Wires
- DIN EN IEC 60228 – Class 5 Copper Conductors
- EN 50575 – CPR Reaction-to-Fire Classification
- IEC 60332-1-2 – Flame Propagation
- VDE 0298-4 – Current-Carrying Capacity Reference
- Building Electrical Installations
- Installation in Protective Conduits
- Closed Installation Ducts
- Electrical Distribution Boards
- Switchgear Internal Wiring
- Machinery Internal Wiring
- Control Cabinet Wiring
- Fixed Protected Electrical Installations