UNIMA CABLE
UNIMA CABLE | Low Voltage Power Cables

CYKY

TECHNICAL DATA SHEET

PVC Insulated and Sheathed Copper Power Cable | 0.6/1 kV

CYKY
PRODUCT DESCRIPTION

CYKY is a low voltage power cable with Class 1 or Class 2 copper conductors, PVC insulation and a black PVC outer sheath. Designed for fixed installations underground, in cable ducts and on support brackets in dry and wet environments where mechanical damage and tensile strain are not expected. Suitable for electricity distribution and industrial power supply.

CABLE CONSTRUCTION
ConductorCopper, Class 1 or 2
Conductor DesignRE / RM / SE / SM
InsulationPVC DIV 1
BeddingElastomeric or Plastomeric Compound or Plastic Tape
Outer SheathPVC DMV 1
Sheath ColourCrna
Core IdentificationHD 308 S2
TECHNICAL DATA
Radni napon0.6/1 kV
Test Voltage4 kV
Max. Conductor Temp.+70°C
Short-Circuit Temp.+160°C
Min. Laying Temperature-5°C
Min. Bending Radius12 × D (Multicore)
CPR razredEca
InstallationFixed
STANDARDS
  • PNE 34 7659-3
  • HD 603 S1
  • EN 60228
  • HD 308 S2
APPLICATIONS
  • Low voltage distribution networks
  • Industrial power installations
  • Electric power stations
  • Underground installations
  • Cable ducts and support brackets
  • Dry and wet environments
  • Industrial control connections
  • Traffic control installations